| NEMA G7 can be used in high temperature applications under humid conditions. It has excellent heat resistance and arc resistance, is self extinguishing, and is rated as class H insulation. It is used in the heating, appliance, and electrical industries; and anywhere a high strength electrical insulator is needed in high temperature applications. |
|
An electrical grade of glass cloth laminate impregnated and cured with silicone resin. |
Sheet sizes 36 x 72, 36 x 48, 48 x 48, 48 x 96, and 48 x 108 in thicknesses .031 in. to 2 in.; cut and fabricated per drawing . |
White |
|
|
|
|
Density |
118 lbs/ft3 - .068 lbs/in3 |
|
Maximum operating temperature |
|
|
electrical |
338° F (170° C) |
|
mechanical |
428° F (220° C) |
|
Water absorption |
0.03% |
|
Hardness (Rockwell M) |
105 |
|
Compressive strength |
41,000 psi |
|
Tensile strength |
20,500 psi |
|
Flexural strength |
25,000 psi |
|
Impact strength - Izod edgewise with grain |
11.0 ft-lb/in. |
|
Dielectric strength |
350 vpm |
|
Dielectric constant (@106 cycles per second) |
4.2 |
|
Volume resistivity |
n/a |
|
Arc resistance |
240 sec |
|
Surface resistivity |
n/a |
|
Parallel dielectric |
60 kv |